FIRE SUPPRESSION SYSTEM INSTALLATION
FIRE SUPPRESSION SYSTEM is comprised of a container
of Ansulex® Low pH liquid re suppression media, a system
pressurization canister and associated plumbing and controls.
Two FUSIBLE LINKS are utilized for automatic actuation, and a
MANUAL PULL STATION for manual actuation. Two NOZZLES
disperse the re suppression media.
The hood is supplied with a eld installed MANUAL PULL STATION,
which must be set-up at the time of the fryer installation by an
authorized Ansul® distributor. See below and following page for
installation details.
If the fryer is installed such that the supplied manual pull station cannot
be installed, a REMOTE MANUAL PULL STATION may be required by
local codes. Any such remote manual pull station must be installed by
an authorized Ansul® distributor in accordance with the AUTHORITY
HAVING JURISDICTION.
When the re suppression system discharges, fryer heating element(s)
and controls are de-energized, and re suppression media discharged.
Fire supression media will form an emulsion designed to both smother
and cool the oil.
The PRIMARY 450ºF FUSIBLE LINK is located on the frypot. This
link will melt and discharge the re suppression system should both
the TEMPERATURE CONTROL THERMOSTAT and the HIGH LIMIT
CONTROL fail. The
SECONDARY 280ºF FUSIBLE LINK is located
in the lter plenum, and will protect against a re in the plenum.
Either link melting will discharge the re suppression media through
both NOZZLES, and cause a buzzer to sound.
The MANUAL PULL STATION and any similar REMOTE MANUAL
PULL STATION will activate the re suppression system when the ring
on the pull station is pulled to its full extent.
DANGER
FIRE HAZARD
Fire suppression system
must be charged and certied
by an authorized Ansul®
distributor.
DO NOT attempt to modify or
bypass the re suppression
system.
An uncontrolled re can
cause serious injury or death.
NOTE:
If the re suppression system
is discharged, a buzzer will
sound continuously. The
fryer will remain inoperable
until the re suppression
system is serviced, recharged
and reset by an authorized
Ansul® distributor.
Charging of the Ansul®
Fire Suppression system
must be in accordance with
Ansul® Design, Installation,
Recharge and Maintenance
Manual, #418087.
NOTE:
If a REMOTE MANUAL PULL
STATION is installed, moving
the FRYER for servicing may
cause the Ansul® system to
discharge. In this case, the
unit must only be installed
with four xed legs
(i.e. remove rear casters and
replace with legs). Additional
legs may be ordered through
an Authorized Wells Service
Agency. See page 19.
INSTALLATION (continued)
8
M381 2M-301603 Owners Manual (Supplemental) NFPA Hood