RW SERIES INSTALLATION MANUAL
Field Connected Water Piping cont.
Before final connection to the unit, the supply and return hose
kits must be connected to each other, bypassing the unit, and
the system flushed to remove dirt, piping chips and other foreign
material. Normally, a combination balancing and close-off (ball)
valve is installed at the return, and a rated gate or ball valve is
installed at the supply. The return valve can be adjusted to obtain
the proper water flow. The valves allow the unit to be removed for
servicing.
The proper water flow must be delivered to each unit whenever the
unit heats or cools. The proper flow rate cannot be accurately set
without measuring the water pressure drop through the refrigerant-
to-water heat exchanger. A3GPMflowrateperton[0.054LPS
perkW]ofcoolingcapacity(2.25GPMperton[0.0404LPSper
kW]minimum)isrequired.
NOTE: The placement and connection of the water circulating
pump(s) must be taken into consideration prior to designing the
final water piping systems.
ClosedLoopTower/BoilerSystems
The water loop is usually maintained between 60°F [15.5°C] and
90°F [32.2°C] for proper heating and cooling operation. This is
accomplished with a cooling tower and a boiler.
To reject excess heat from the condenser water loop, the use of a
closed-circuit evaporative cooler or an open type cooling tower with
a secondary heat exchanger between the tower and the condenser
water loop is recommended. If an open type cooling tower is
used without a secondary heat exchanger, continuous chemical
treatment and filtering of the water must be performed to ensure
the water is free from damaging materials.
CAUTION:Waterpipingexposedtooutside
temperaturemaybesubjecttofreezing.
OpenLoopWellWaterSystems
Installation of an open loop system is not recommended without
using a secondary heat exchanger unless water quality guidelines
are met.
EarthCoupledSystems
All supply and return water piping should be insulated to prevent
excess condensation from forming on the water lines. Ensure
pumping system is capable of providing adequate flow rate at
the system pressure drop, 3.0 GPM per ton [0.054 LPS per kW]
(source side) is recommended. Antifreeze in the loop is strongly
recommended.
HeatingwithHighSourceTemperatures
Heating water with a water to water unit using high source
temperatures can lead to operating conditions that fall outside
of the system operating range. The condition occurs when the
loop (source) temperature exceeds 70°F [21.1°C] with a full
flow of 3 GPM per ton [0.054 LPS per kW]. Under this scenario,
the evaporating temperature can fall outside of the compressor
operating window.
To allow the system to operate correctly, restricting the source side
flow when the evaporating temperature exceeds 55°F [12.7°C] is
recommended. One way of accomplishing this is to use a flow-
restricting valve on the source loop circuit that is controlled by
the evaporating temperature. Locate the sensing device on the
refrigerant inlet of the evaporator. In dual circuit systems, the
company recommends monitoring both circuits and controlling off
the sensor that reads the highest temperature.
As an alternative to the evaporating temperature, the suction line
temperature can be monitored with the same control capability. In
this control, temperature should be a maximum of 65°F [18.3°C].