RW SERIES INSTALLATION MANUAL
General
System piping should be kept as simple as possible to minimize
the pressure drop, but hand valves should be field installed to
facilitate unit servicing. The piping installation should provide
service personnel with the ability to measure and/or monitor water
temperatures and pressures.
Source and load fluid connections are provided with 2 in. [50.8
mm] Victaulic grooved nipples (see Figure 4). Each nipple will also
have a PT port installed for test and balance purposes. It will be the
installing contractor’s responsibility to adequately support incoming
piping to avoid damage to the unit’s piping or heat exchangers. The
water lines should be routed so as not to interfere with access to
the unit.
Field Connected Water Piping
Figure 4: Water Connections (RWXW360 shown)
P/T Plug
2 in. Victaulic
Grooved
Nipples
Figure 5: Chiller Back View (RWXW360 shown)
Water
Connection
Ports
Out
In
In
Out
Brazed Plate Heat Exchanger
Optional Connection Kit
CKV160FL (Includes four
of each)
TKC16S-4
(1 of 4)
CAUTION:Removetheplasticprotectivecapsintheendsofeachofthefourwaterpipesontheheatexchangers
priortopipingconnection.Failuretoremovethecapswillresultinseriousdamageandcouldvoidthewarranty.
For any installation where the transmission of vibration through
the piping connections could cause unacceptable noise levels
in occupied spaces it is important to provide adequate vibration
damping. One method is to use the optional Adapter Hose Kit (kit
number TKC16S-4). This Kit consists of four pieces of a braided
stainless steel flexible hose with a 2 in. Victaulic connection on
one end and a 2 in. MPT connection with pipe union on the other.
Overall length of each piece is 18 in.
NOTE: Units are factory run-tested using propylene glycol. Prior to
connecting piping to unit, thoroughly flush heat
exchangers.