Page 1 - Model WMC-145SBS to 400DBS

Installation Manual IM 1029-2 Group: Chiller Part Number: 331374611 00 Effective: January 2013 Supersedes: October 2012 Magnitude™ Magnetic Bearing C

Page 2 - Table of Contents

10 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 Mounting/Lifting/Total Weights Drawings are for reference only and are not in

Page 3 - W M C 290 D BS

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 11 Chiller Dimensions Figure 5, WMC 145D, 2 Pass (See page 17 for notes.)

Page 4 - Installation

12 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 Figure 6, WMC 145S, 2 Pass (See page 17 for notes.)

Page 5 - Location and Mounting

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 13 Figure 7, WMC 150D, 2-Pass (See page 17 for notes.)

Page 6 - Filtering and Treatment

14 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 Figure 8, WMC 250D, 2-Pass (See page 17 for notes.)

Page 7 - Condenser Water Temperature

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 15 Figure 9, WMC 290D, 2-Pass (See page 17 for notes.)

Page 8 - Field Insulation

16 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 Figure 10, WMC 400D, 2-Pass (See page 17 for notes.)

Page 9 - Physical Data and Weights

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 17 Drawing Notes NOTES: 1. All dimensions are in inches and [millimeters] unless

Page 10 - 332834901

18 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 Pressure Drop Curves NOTE: The Evaporator and Condenser Model Codes are shown

Page 11 - Chiller Dimensions

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 19 Figure 13, 2-Pass Evaporators WMC Evap - Water Side Pressure Drop(2 pass)010

Page 12

2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 Table of Contents Introduction ... 3Nom

Page 13

20 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 Figure 15, 3-Pass Evaporators WMC Evap - Water Side Pressure Drop(3 pass)0102

Page 14

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 21 Relief Valves As a safety precaution and to meet code requirements, each chi

Page 15

22 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 Sizing Vent Piping (ASHRAE Method) Relief valve pipe sizing is based on the di

Page 16

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 23 Electrical Information Wiring, fuse and wire size must be in accordance with

Page 17 - Harmonic Filter Dimensions

24 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 Case 2, WMC 145D – 400D Field Power Wiring Case 2 adds optional factory-mount

Page 18 - Pressure Drop Curves

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 25 Case 3, WMC 250D, 290D, 400D Field Power Wiring Case 3 adds the combo harmon

Page 19 - CPD - ft

26 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 Case 4, WMC 250D, 290D, 400D Field Power Wiring Case 4 adds both the EMI filt

Page 20 - (3 pass)

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 27 Case 5, WMC 145D – 150D Field Power Wiring Case 5 adds remote-mounted combo ha

Page 21 - Relief Valves

28 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 Case 6, WMC 145D – 150D Field Power Wiring Refer to Case 5. Case 6 merely add

Page 22 - Common Piping

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 29 Figure 24, Case 8 WMC 145S Field Power Wiring NOTES: 1. Not applicable 2. R

Page 23 - Electrical Information

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 3 Introduction General Description The Daikin Magnitude™ Frictionless Centrifugal

Page 24

30 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 Optional Harmonic Filter The optional harmonic filters are field mounted and

Page 25

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 31 Electrical Data General Note: The RLA for use in the following tables is obtai

Page 26

32 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 Table 9, WMC 145S-B, 3/50/400 SINGLE POINT CONNECTION, STANDARD COMPRESSOR CH

Page 27

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 33 Table 12, WMC 145D-B & WMC 150D-B, 3/60/460 (Continued) MULTI-POINT CONNE

Page 28

34 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 Table 14, WMC 145D-B & WMC 150D-B, 3/50/400 SINGLE POINT CONNECTION, STAN

Page 29

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 35 WMC 250D & 290D, Dual Compressor Table 15, WMC 250D-B & WMC 290D-B, 3

Page 30 - Optional Harmonic Filter

36 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 Table 16, WMC 250D-B & WMC 290D-B, 3/50/400 SINGLE POINT CONNECTION, STAN

Page 31 - MC 145S, Single Compressor

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 37 Table 17, WMC 250D-B & WMC 290D-B, 3/50/380 SINGLE POINT CONNECTION, STA

Page 32 - Continued next page

38 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 WMC 400D 3/60/460 ONLY Table 18, WMC 400D-B, 3/60/460 SINGLE POINT CONNECTION

Page 33

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 39 Figure 25, Power Panel (Front End Box) Power Cable Entrance Access Plate

Page 34

4 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 Installation Receiving and Handling The unit should be inspected immediately af

Page 35

40 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 Figure 26, Control Panel Terminal Board TB UTB1 for Field Wiring Connections

Page 36

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 41 Figure 27, Field Control Wiring Diagram NOTE: Complete notes are on the follo

Page 37

42 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 Field Wiring Diagram Notes 1. Compressor front end box is factory mounted and

Page 38 - WMC 400D 3/60/460 ONLY

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 43 Control Wiring The control circuit on the Daikin centrifugal packaged chiller

Page 39

44 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 EMI Radiated EMI is similar to an unwanted radio broadcast being emitted from

Page 40 - Figure 26, Control Panel

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 45 Multiple Chiller Setup WMC units have their control components factory wired t

Page 41

46 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 MicroTech II Operator Interface Touch Screen (OITS) Settings Settings for any

Page 42 - Field Wiring Diagram Notes

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 47 Prestart System Checklist Yes No N/A Chilled Water Piping complete ...

Page 43 - VFD Line Harmonics

48 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 Long Term Storage This information applies to new units being stored waiting f

Page 44 - System Pumps

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 49 Operation Operator Responsibilities It is important that the operator become f

Page 45 - Communication Setup

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 5 Location and Mounting Location WMC chillers are intended only for installation

Page 46 - Operating Sequence

50 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 Since there are many other factors that can influence performance, systems may

Page 47 - Prestart System Checklist

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 51 Transfer Back to Grid Power: Proper transfer from stand-by generator power bac

Page 48 - Long Term Storage

52 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 Connection to Chiller Connection to the chiller for all BAS protocols will be

Page 49 - Operation

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 53

Page 50 - Use with On-Site Generators

© Daikin • www.DaikinApplied.com • (800) 432-1342 IM 1029-2 (1/13) Daikin Learning Institute Now that you have made an investment in modern, efficien

Page 51 - Building Automation Systems

6 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 size and type required. Victaulic connections are AWWA C-606 on 14-inch and lar

Page 52 - Protocols Supported

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 7 Flow Switch Note: Chiller units must have flow switches for the evaporator and

Page 53

8 Magnitude™ Frictionless Centrifugal Chillers – Model WMC IM 1029-2 !CAUTION Tower water treatment is essential for continued e

Page 54 - IM 1029-2 (1/13)

IM 1029-2 Magnitude™ Frictionless Centrifugal Chillers – Model WMC 9 Physical Data and Weights With positive pressure systems, the pressure varianc